Installation instructions geoTHERM VWS/VWW 0020057444_0166
8.10 Parameters that can be set with
vrDIALOG 810/2
Using its computer-supported graphics visualisation and
configuration, vrDIALOG 810/2 (eBUS) enables you to
optimise heating appliances and control systems and
thus make use of their energy saving potential. Both of
them enable you to create a visual impression of the
processes in your control system and influence them at
any time. The programmes enable you to record and
graphically prepare system data, to load device configu-
rations and change and save them online and to save in-
formation in the form of reports.
Using vrDIALOG 810/2, you can make all the settings for
the heat pump as well as other settings for optimisation.
Settings via vrDIALOG may only be performed by an ex-
perienced specialist.
Parameters Description Factory setting
Calibration of temperature sensors Internal sensors can only be calibrated via vrDIA-
LOG 810/2.
Change name: CH circuit A maximum of ten
letters are available per heating circuit for this purpose. A
maximum of ten letters are available per heating circuit
for this purpose. The selected names are saved automati-
cally and displayed on the corresponding displays.
Depending on the system configuration, the names of ad-
ditional heating circuits appear in the display.
HK2: <HK2>
Software version The status provides information about the operating state
of the heat pump software.
—
Elec Tariff switch Status of power interruption due to activation of the EVU
contact (blocking initiated by the power company):
"no" = no blocking, "yes" = blocking active, activation by
means of e.g. ripple control signal/receiver.
—
Phase Status Phase status: displays whether all 3 phases are present
(OK/Error).
—
Phase Sequence Phase sequence: displays whether the phase sequence is
correct (OK/Error).
—
Starting current limiter Soft start status: ON/OFF —
Fixed value day
Fixed value night
This display only appears if the setting Type "Fixed value"
has been selected via vrDIALOG.
Here the flow temperature is controlled around a fixed
setpoint, independently of the outside temperature.
Fixed value day: Flow setpoint temperature (e.g. for
manually set screed floor drying).
Fixed value night: Flow setpoint temperature at night.
35 °C
30 °C
Type HK2 Setting the heating circuit type:
– Direct circuit: (Hydraulic plan 3) Heating mode runs
with the setpoint flow temperature determined by the
weather-controlled energy balance controller.
– Mixer circuit: (Hydraulic plan 4) Heating mode runs
with the setpoint flow temperature determined by the
weather-controlled controller.
– Fixed value: Fixed settings for the setpoint flow temper-
atures for day and night; see Menu C5.
direct circuit
Table 8.7 Parameters that can be set with vrDIALOG 810/2
8 Controller