59Installation instructions geoTHERM VWS/VWW 0020057444_01
Display shown Description Factory setting
Menu D: Perform diagnostics In Menus D1 to D5 you can operate and test the heat
pump in diagnostic mode.
The diagnostic menus cannot be exited with any set-
ting apart from "Test = no" (Menu D1). An auto reset
occurs 15 minutes after the last button is actuated.
In the diagnostic mode, the pre-, minimum and
run-on times of the compressor, pumps and other
components are not heeded!
Malfunctions can occur if the diagnostic mode is fre-
quently turned on and off.
diagnosis
D1
refrigerant circuit
Test >no
Comp High Pressure 11.9 bar
T outlet compresor 66 °C
Comp. low pressure 2.3 bar
T inlet compressor 0 °C
Test: no/off/heating/hot water/cooling
1)
*
. Set the
operating mode for the heat pump in order to test
its behaviour.
Comp. high pressure: Display of coolant pressure
Compressor output.
T outlet compressor (compressor output, high pres-
sure): Display of temperature sensor T1.
*
Comp. low pressure:Display of coolant pressure
Compressor input.
T inlet compressor (compressor input, intake side):
Display of temperature sensor T2.
*
—
diagnosis
D2
refrigerant circuit
overheat 4 K
Subcooling 10 K
Temp TEV inlet 10 °C
Superheating of the coolant calculated from T2
*
and
low pressure sensor. Only displayed when the com-
pressor is operating.
Subcooling of the coolant calculated from T4
*
and
high pressure sensor. Only displayed when the com-
pressor is operating.
Temp TEV inlet: Temperature at the inlet of the
thermal expansion valve
*
—
diagnosis
D3
Central Heating
Current flow temp. 27 °C
Current return temp 24 °C
CH pump Off
CH pressure 1.2 bar
Auxiliary heater Off
Current flow temperature T6.
*
Current return temperature T5.
*
Status of CH pump: ON/OFF
CH pressure (heating circuit pressure sensor).
Status of auxiliary heating: ON/OFF
—
diagnosis
D4
Heat Source
Brine pump On
T Return Source 10 °C
T outlet Evaporator 9 °C
Brine pressure 1.5 bar
Status of brine pump: ON/OFF
T return source: Temperature of the heat source,
T3.
*
T outlet evaporator: Heat source temperature at
the outlet of the heat pump, T8.
*
VWS only:
Brine pressure (Pressure sensor for heat source cir-
cuit; brine pressure)
—
Table 8.4 Parameters that can be set in the Code level (cont.)
1)
Cooling mode is only possible when using the VWZ NC 14/17 ac-
cessory, and only for VWS 14 and VWS 17 heat pumps.
*
see Figs. 1 and 2 in the appendix