Installation instructions geoTHERM VWS/VWW 0020057444_0130
6.6 Controller PCB at a glance
1
L L L L L 1 L N N N N N 2 N 2 1 2 1 L N
2 3 4 5 S CH 6 7 8
A SB
N N A uf Z u L N 1 2 1 2 1 2 1 2 1 2 1 2
DCF O T AF
- +
A uf Z u
ZH
N L
ZP
N L
SK 2 -P
N L
HK 2 -P HK2 VF2 RF1 VF1 SP BUS DC F / AF E VU 1xZP L P /UV 1
1
2 3 4 5 6 7 8 9 10 11 12 13 14
21
33 32 31 30 29 28 27 26 25 24
15
16
18
17
19
22
23
20
Fig. 6.6 Controller PCB
Key to Fig. 6.6
Upper connection terminals
1 <ZH> Electric auxiliary heating
2 LP / UV 1 3-port diverter valve for hot water generation
3 <ZP> Circulation pump for hot water
4 <SK2-P> VWW only: Well pump contactor
5 <HK2-P> External (second) heating circuit pump
6 <HK2> 3-way mixer valve
7 VF2 External flow sensor
8 RF1 Buffer cylinder base temperature sensor
9 VF1 Buffer cylinder head temperature sensor
10 SP DHW cylinder temperature sensor
11 BUS eBUS
12 DCF / AF Outside temperature sensor + DCF signal
13 EVU EVU contact (supply interruption, ripple control sig-
nal from power company)
open: compressor operation permitted
closed: compressor operation blocked
14 1xZP Contact for non-recurring request for the
circulation pump, e. g. via pushbutton
PCB components
15 eBUS/vrDIALOG
16 eBUS address rotary switch, set to "1" (factory setting)
17 Fuse T 4A/250 V
18 Check LED for power supply (lights green if OK)
19 Fuse T 4A/250 V for brine pump
20 Monitoring of compressor phase sequence
21 Controller plug (User Interface)
22 Sensor connection plug 1
23 Sensor connection plug 2
Lower connection terminals
24 ASB Starting current limiter
25 8 Compressor contactor
26 7 Pressure switch
27 6 (not connected)
28 SCH Accessory - brine pressure switch (VWW: Flow switch)
29 5 Brine pump (VWS only)
30 4 Voltage supply
31 3 Internal heating circuit pump
32 2 unused
33 1 unused
The controller PCB has a protective cover plate which
has cut-outs for the eBUS/vrDIALOG (Item 15) connec-
tion, as well as for the power supply LED (Item 18).
The cover plate must be removed to change the fuses,
Items 17 and 19.